Power Modular Concept PMC 12, single-phase UPS up to 12 kVA

The single-phase double conversion UPS (VFI-SS 111) is designed for use as a floor-standing enclosure and for 482.6 mm (19") installation. A display which may be rotated through 90° ensures optimum operation in both installation positions. As well as integral batteries which may be replaced in "hot swap" mode with the system operational, the 1 – 3 kVA UPS systems also offer a USB port and two switchable EN 60 320 C13 outputs. The parallel-redundant 4.5 and 6 kVA UPS systems have the “hot swap” functionality of the batteries in the external battery housing. Parallel redundancy switching of up to 3 UPS systems makes it possible to achieve outputs of up to 12 kVA in parallel mode and in N+1 redundant mode. Communication is via a serial interface. With all UPS systems, the use of an optional SNMP card is supported, which facilitates communication via the network.

• High-quality double-conversion technology with optimum sinusoidal output voltage
• Autonomy time may be extended with battery expansion packs
• For use in a rack or as a stand-alone enclosure
• Output classes 1, 2, 3, 4,5 and 6 kVA
• Parallel switching of the 4.5 and 6 kVA versions up to 12 kVA N+1 redundant
• Intelligent battery management system monitors battery charging and ensures system
   availability. Further protection from overloading and exhaustive discharge.
• Software compatibility in all standard operating systems included with the supply

PMC 12, single-phase, 1 kVA, 2 kVA, 3 kVA

• LCD display rotatable through 90°
• Designed for rack and tower operation
• Internal "hot swap" battery packs replaceable
  from the front
• Two switchable EN 60 320/C13 outputs
• Serial and USB interface for communication
• Emergency Power Off (EPO)
• Autonomy may be extended with additional external
   battery modules
• Input power factor > 0.99
• Large input voltage range from 160 to 288 V
• Optional external bypass
• Outputs 1 and 2 kVA: 4 x C13 static, 2 x C13
  switchable
• Outputs 3 kVA: 2 x C13, 1 x C19, 2 x C13 switchable


Block diagram parallel-redundant UPS 4.5/6 kVA
PMC 12, single-phase, 4.5 kVA, 6 kVA

• LCD display rotatable through 90°
• Parallel switching up to 12 kVA N+1 redundant
• Designed for rack and tower operation
• External 3 U "hot swap" battery modules, replaceable
  from the front
• Serial interface for communication
• Autonomy may be extended with additional external
   battery modules
• Input power factor > 0.99
• Large input voltage range from 160 to 288 V

The plug-in power distribution system PSM 32 A is perfectly tailored to the demands of information technology. The parallel hot swap punched section for two UPS may be used directly with the PSM rail 32 A. The punched section with three connections requires a sub-distributor which offers two 32 A CEE outputs plus four EN 60 320/C20 outputs, each with fuse.

Autonomy (min) at 100% load:
USP type Supplied state Battery packs
1 2 3
1 kVA 7 min 1:09 h 2:13 h
2 kVA 7 min 34 min 1:09 h
3 kVA 5 min 30 min 1:02 h
4.5 kVA 12 min 31 min 54 min
6 kVA 8 min 20 min 36 min
Power Modular Concept PMC 12, single-phase UPS up to 12 kVA